UL Listings |
Use the chart to find the right listing for your applications. |
Use the quick links below or scroll down to find the right category. |
|
|
ARCHITECTUAL |
Use these links to see our other Listings.
ELECTRICAL LISTING CHART
HOURLY FIRE RATING |
PENETRATION
(Up to Size & Type) |
FIRE-RATED FLOOR / WALL ASSEMBLY |
OPTIONAL
SLEEVING
(Type) |
RECTANGULAR OR CORED OPENING
(Up to Size) |
UL SYSTEM Nos. |
SELF SEAL®
PRODUCT CODE |
CONCRETE – METALLIC EMT and CONDUIT |
3 |
Blank Opening |
Concrete Slab /
Block Wall |
Steel, PVC |
6 in. diam |
C-AJ-0048 |
SL-100 / MW-300 (Floors only)
GG-200 / MW-300 (Walls and Floors) |
3 |
4" EMT or Conduit |
Concrete Slab /
Block Wall |
Steel, PVC |
6 in. diam |
C-AJ-1227 |
SL-100 / MW-300 (Floors only)
GG-200 / MW-300 (Walls and Floors) |
2 and 3 |
4” EMT / 6” Conduit |
Concrete Slab / Block Wall |
Steel |
8-1/2 in. diam |
C-AJ-1369 |
SL-100 / MW-300 (Floors only)
GG-200 or GG-266 / MW-300 (Walls and Floors) |
2 |
4” EMT / 6” Conduit |
2-1/2” Concrete Slab |
No |
8-1/2 in. diam |
C-AJ-1452 |
SL-100, GG-200 or GG-266 / MW-300 |
2 (T Rating) |
4”EMT / 6” Conduit |
Concrete Slab / Block Wall |
No |
8-1/2 in. diam |
C-AJ-1554 |
SL-100 / MW-300 (Floors only)
GG-200 or GG-266 / MW-300 (Walls and Floors) |
2 |
4” EMT / 6” Conduit |
Concrete Slab |
No |
8-1/2 in. diam |
F-A-1021 |
GG-200 / MW-300 (Underside Floor Application) |
2 |
4” EMT / 6” Conduit |
Concrete Slab |
No |
8-5/8 to 9-1/8 in. Cone Shape |
F-A-1055 |
SL-100, GG-200 or GG-266 / MW-300 (Floors only) |
1 and 2 |
4" EMT or Conduit |
Hollow-Core Floor / Block Wall |
No |
6 in. diam |
C-AJ-1201 |
GG-200 or GG-266 |
1 and 2 |
4” EMT or Conduit (45° Angle) |
Concrete or Block Wall |
No |
5-1/2 in. diam |
W-J-1141 |
GG-200 or GG-266 (Walls only) |
2 |
4” EMT / 6” Conduit |
Concrete Slab / Block Wall |
No |
8-1/2 in. diam |
C-AJ-1370 |
GG-266 |
2 |
Multiple 4” EMT or Conduit |
2-1/2” Concrete Slab / Block Wall |
No |
216 sq. in. |
C-AJ-1393 |
SL-100 / MW-300 (Floors only)
GG-200 or GG-266 / MW-300 (Walls and Floors) |
2 |
4" EMT or Conduit |
Concrete Slab /
Block Wall |
No |
24 sq. ft. |
C-AJ-8048 |
SL-100 / MW-300 (Floors only)
GG-200 / MW-300 (Walls and Floors) |
2 |
4” EMT / 6” Conduit |
Metal Deck |
Steel |
8-1/2 in. diam |
F-A-1026 |
SL-100, GG-200 or GG-266 / MW-300 |
1 |
4” EMT or Conduit |
Concrete Slab – Drywall Ceiling |
No |
5-1/2 in. diam |
F-E-1019 |
GG-200 or GG-266 |
- TOP -
CONCRETE – NONMETALLIC CONDUIT |
2 |
Multiple 1” ENT |
Concrete Slab / Block Wall |
No |
4-1/8 in. diam |
C-AJ-2442 |
GG-266 |
2 (T-Rating) |
Multiple 1” ENT and BX Cables |
Concrete Slab / Block Wall |
No |
8-1/2 in. diam |
C-BJ-8022 |
SL-100 / MW-300 (Floors only)
GG-200 / MW-300 (Walls and Floors) |
1, 2 and 3 |
2” ENT, FNMC, PVC Conduit |
Hollow-Core Floor / Block Wall |
Steel |
3 in. diam |
C-AJ-2314 and
C-AJ-2587 |
GG-266 |
2 and 3 |
2” ENT, FNMC, PVC Conduit |
Concrete Slab |
Steel |
3 in. diam |
C-AJ-2315 and
C-AJ-2585 |
GG-266 |
2 |
2” ENT, FNMC, PVC Conduit |
2-1/2” Concrete Slab |
No |
3 in. diam |
C-AJ-2406 |
GG-266 |
2 |
2” PVC Conduit |
Concrete Slab / Block Wall |
No |
4 in. diam |
C-AJ-2537 |
GG-266 |
2 |
2” ENT, FNMC, PVC Conduit |
2-1/2” Concrete Slab |
No |
3 in. diam |
F-A-2105 |
SL-100, GG-200 or GG-266 / FIREBAND |
2 |
2” ENT, FNMC, PVC Conduit |
Concrete Slab |
No |
2-1/2 to 3-1/4 in. Cone Shape |
F-A-2116 |
GG-266 |
2 |
3” PVC Conduit |
Concrete Slab |
No |
5 to 5-1/4 in. Cone Shape |
F-B-2024 |
GG-266 |
2 |
4” PVC Conduit |
Concrete Slab |
No |
5-1/2 to 6-1/4 in. Cone Shape |
F-B-2028 |
GG-266 |
2 |
4” PVC Conduit |
Concrete Slab / Block Wall |
No |
6-1/4 in. diam |
C-BJ-2027 |
GG-266 |
2 |
2” ENT, FNMC / 3” PVC Conduit |
Concrete Slab / Block Wall |
No |
4-5/8 in. diam |
C-AJ-2439 |
GG-200 or GG-266 / FIREBAND |
3 |
4” PVC Conduit |
Concrete Slab / Block Wall |
No |
5 in. diam |
C-AJ-2207 |
GG-200 or GG-266 / TYPE-SSC |
2 |
6” PVC Conduit |
Concrete Slab / Block Wall |
No |
7 in. diam |
C-AJ-2584 |
GG-200 or GG-266 / TYPE-SSC |
2 |
2” ENT, FNMC, PVC Conduit |
Metal Deck |
No |
3 in. diam |
C-AJ-2406 |
GG-266 |
2 |
2” ENT, FNMC / 4” PVC Conduit |
Metal Deck |
No |
5 in. diam |
F-A-2086 |
GG-200 / GG-266 / TYPE-SSC |
2 |
3” and 4” PVC Conduit |
Metal Deck |
Steel (Req’d) |
6 in. diam |
F-A-2133 |
GG-266 / TYPE-SSR / MW-300 |
1 |
4” PVC Conduit |
Concrete Slab – Drywall Ceiling |
No |
5 in. diam |
F-E-2023 |
GG-266 / TYPE-SSC |
- TOP -
GYPSUM WALLBOARD – METALLIC EMT and CONDUIT |
1 |
Blank Opening |
G.W.B. |
No |
15 sq. in. |
W-L-0028 |
GG-200 / Type-X Board |
1 |
Multiple 2” EMT or Conduit |
G.W.B. |
No |
36 sq. in. |
W-L-1366 |
GG-200 or GG-266 / MW-300 |
1 and 2 |
4" EMT or Conduit |
G.W.B. |
No |
6 in. diam |
W-L-1086 |
GG-200 |
1 and 2 |
4” EMT or Conduit (45° Angle) |
G.W.B. |
No |
5-1/2 in. diam |
W-L-1316 |
GG-200 or GG-266 |
1 and 2 |
4” EMT or Conduit |
Shaft Wall |
Steel (Req’d) |
11 in. diam |
W-L-1364 |
GG-200 / MW-300 |
1 and 2 |
4" EMT or Conduit |
G.W.B. |
No |
585 sq. in. |
W-L-8012 |
GG-200 / MW-300 |
GYPSUM WALLBOARD – NONMETALLIC CONDUIT |
1 and 2 |
2” PVC Conduit |
G.W.B. |
No |
3 in. diam |
W-L-2145 |
GG-266 |
1 and 2 |
2” PVC Conduit |
Shaft Wall |
No |
3 in. diam |
W-L-2417 |
GG-266 / FIREBAND |
1 and 2 |
4” PVC Conduit |
G.W.B. |
No |
5 in. diam |
W-L-2143 |
GG-200 or GG-266 / TYPE-SSC |
FRAMED FLOOR – METALLIC EMT and CONDUIT / NONMETALLIC CONDUIT, ELECTRICAL CABLES |
1 |
4” EMT or Conduit (Optional Chase Wall) |
Wood Floor |
No |
5-1/2 in. diam |
F-C-1093 |
GG-200 |
1 |
4” EMT or Conduit (Optional Chase Wall) |
ISPAN System |
No |
5-1/2 in. diam |
F-C-1151 |
GG-200 |
1 |
2” ENT, FNMC, PVC Conduit (Optional Chase Wall) |
Wood Floor |
No |
3 in. diam |
F-C-2200 |
GG-266 |
1 |
4” PVC Conduit (OptionalChase Wall) |
Wood Floor |
No |
5 in. diam |
F-C-2227 |
GG-266 / TYPE-SSC |
1 |
Elect. / Comm. Cables (Optional Chase Wall) |
Wood Floor |
No |
3 in. diam |
F-C-3076 |
GG-200 |
1 |
Elect. / Comm. Cables (Optional Chase Wall) |
ISPAN System |
No |
3 in. diam |
F-C-3100 |
GG-200 |
- TOP -
CONCRETE and GYPSUM WALLBOARD – ELECTRICAL CABLES, CABLE TRAYS and BUSWAYS |
3 |
Elect. / Comm. Cables |
Concrete Slab /
Block Wall |
Steel, PVC |
6 in. diam |
C-AJ-3113 |
SL-100 / MW-300 (Floors only)
GG-200 / MW-300 (Walls and Floors) |
1 and 2 |
Elect. / Comm. Cables |
Hollow-Core Floor / Block Wall |
No |
4 in. diam |
C-AJ-3102 |
GG-200 |
2 |
BX Cables |
Concrete Slab / Block Wall |
No |
5 in. diam |
C-AJ-3251 |
SL-100 / MW-300 (Floors only)
GG-200 / MW-300 (Walls and Floors) |
1 |
NM Cables |
Hollow-Core Floor / Block Wall |
No |
3 in. diam |
C-AJ-3255 |
GG-200 |
2 |
Elect. / Comm. Cables |
Metal Deck |
No |
4 in. diam |
F-A-3011 |
SL-100 or GG-200 / MW-300 |
1 |
Elect. / Comm. Cables |
Concrete Slab – Drywall Ceiling |
No |
3 in. diam |
F-E-3013 |
GG-200 |
1 and 2 |
Elect. / Comm. Cables |
G.W.B. |
No |
4 in. diam |
W-L-3067 |
GG-200 |
1 and 2 |
Metal-Clad Cable |
G.W.B. |
No |
2 in. diam |
W-L-3083 |
GG-200 |
1 |
NM Cables |
G.W.B. |
No |
3 in. diam |
W-L-3290 |
GG-200 |
1 |
Elect / Comm. Cables |
G.W.B. |
No |
48 sq. in. |
W-L-3305 |
GG-200 / MW-300 |
2 |
36" Aluminum / Steel
Cable Trays |
Concrete Slab /
Block Wall |
No |
960 sq. in. |
C-AJ-4036 |
SL-100 / MW-300 (Floors only)
GG-200 / MW-300 (Walls and Floors) |
2 |
36" Aluminum / Steel
Cable Trays |
Concrete Slab /
Block Wall |
No |
24 sq. ft. |
C-AJ-8048 |
SL-100 / MW-300 (Floors only)
GG-200 / MW-300 (Walls and Floors) |
1 and 2 |
18” Aluminum / Steel Cable Trays |
G.W.B. |
No |
585 sq. in. |
W-L-4036 |
GG-200 / MW-300 |
2 |
27” Busway |
Concrete Slab / Block Wall |
No |
360 sq. in. |
C-AJ-6024 |
SL-100 / MW-300 (Floors only)
GG-200 / MW-300 (Walls and Floors) |
1 and 2 |
23” Busway |
G.W.B. |
No |
364 sq. in. |
W-L-6007 |
GG-200 / MW-300 |
- TOP -
MECHANICAL LISTING CHART
HOURLY FIRE RATING |
PIPE PENETRATION
(Up to Size & Type) |
PIPE INSULATION
(Type) |
FIRE-RATED
FLOOR / WALL
ASSEMBLY |
OPTIONAL
SLEEVING
(Type) |
RECTANGULAR OR CORED OPENING
(Up to Size) |
UL SYSTEM Nos. |
SELF SEAL®
PRODUCT CODE |
CONCRETE – METALLIC PIPE and DUCTWORK |
3 |
Blank Opening |
No |
Concrete Slab /
Block Wall |
Steel, PVC |
6 in. diam |
C-AJ-0048 |
SL-100 / MW-300 (Floors only)
GG-200 / MW-300
(Walls and Floors) |
3 |
3" Copper / 4" Steel / 4” Cast Iron (Shielded Coupling) |
No |
Concrete Slab /
Block Wall |
Steel, PVC |
6 in. diam |
C-AJ-1227 |
SL-100 / MW-300 (Floors only)
GG-200 / MW-300
(Walls and Floors) |
2 and 3 |
4” Copper / 8” Steel |
No |
Concrete Slab / Block Wall |
Steel |
10-1/2 in. diam |
C-AJ-1369 |
SL-100 / MW-300 (Floors only)
GG-200 or GG-266 / MW-300 (Walls and Floors) |
2 |
4” Copper / 8” Steel |
No |
2-1/2” Concrete Slab |
No |
10-1/2 in. diam |
C-AJ-1452 |
SL-100, GG-200 or GG-266
/ MW-300 |
2
(T Rating) |
4” Copper / 10” Steel |
2” or 3” Mineral Fiber |
Concrete Slab / Block Wall |
No |
12 in. diam |
C-AJ-1554 |
SL-100 / MW-300 (Floors only)
GG-200 or GG-266 / MW-300 (Walls and Floors) |
2 |
4” Copper / 8” Steel |
No |
Concrete Slab |
No |
10-1/2 in. diam |
F-A-1021 |
GG-200 / MW-300 (Underside Floor Application) |
2 |
4” Copper / 8” Steel |
No |
Concrete Slab |
No |
8-5/8 to 9-1/8 in. Cone Shape |
F-A-1055 |
SL-100, GG-200 or GG-266 / MW-300 (Floors only) |
2 |
3” Copper / 3” Steel |
1” Glass Fiber |
Concrete Slab / Block Wall |
Steel |
6 in. diam |
C-AJ-5163 |
SL-100 / MW-300 (Floors only)
GG-200 or GG-266 / MW-300
(Walls and Floors) |
3 |
3" Copper / 4" Steel |
1” Mineral Fiber |
Concrete Slab /
Block Wall |
Steel, PVC |
6 in. diam |
C-AJ-5092 |
SL-100 / MW-300 / PI-400 (Floors only)GG-200 / MW-300 / PI-400 (Walls and Floors) |
2 |
16” Steel |
1” or 1-1/2” Mineral Fiber |
Concrete Slab / Block Wall |
No |
576 sq. in. |
C-AJ-5093 |
SL-100 / MW-300 / PI-400 (Floors only) GG-200 / MW-300 / PI-400 (Walls and Floors) |
2 and 3 |
3” Copper / 8” Steel |
1”, 1-1/2” or 2” Glass Fiber |
Concrete Slab / Block Wall |
No |
14 in. diam |
C-AJ-5204 and
C-AJ-5307 |
GG-266 / MW-300 |
2 |
6” Copper / 16” Steel |
1-1/2”, 2”, 2-1/2” or 3” Cellular Glass Insulation |
Concrete Slab / Block Wall |
Steel |
24 in. diam |
C-AJ-5228 |
SL-100 / MW-300 (Floors only)
GG-200 or GG-266 / MW-300 (Walls and Floors) |
2
(T Rating) |
4” Copper / 8” Steel with Optional Pipe Fittings |
2” or 3” Mineral Fiber |
Concrete Slab / Block Wall |
No |
10 in. diam |
C-AJ-5229 |
SL-100 / MW-300 (Floors only)
GG-200 or GG-266 / MW-300 (Walls and Floors) |
2
(T Rating) |
4” Copper, Steel, Cast Iron |
3/4” AB / PVC Flexible Foam |
Concrete Slab / Block Wall |
No |
8 in. diam |
C-AJ-5293 |
GG-266 / MW-300 (Walls and Floors) |
1 and 2 |
3" Copper / 4" Steel |
No |
Hollow-Core Floor / Block Wall |
No |
6 in. diam |
C-AJ-1201 |
GG-200 or GG-266 |
1 and 2 |
4” Copper / 4” Steel (45° Angle) |
No |
Concrete or Block Wall |
No |
5-1/2 in. diam |
W-J-1141 |
GG-200 or GG-266 (Walls only) |
2 |
4” Copper / 8” Steel |
No |
Concrete Slab / Block Wall |
No |
10-1/2 in. diam |
C-AJ-1370 |
GG-266 |
1 and 2 |
Multiple 1” Gas Tubing |
No |
Hollow-Core Floor / Block Wall |
No |
4 in. diam |
C-AJ-1553 |
GG-266 |
2 |
Multiple 3” Copper / 4” Steel |
No |
2-1/2” Concrete Slab / Block Wall |
No |
216 sq. in. |
C-AJ-1393 |
SL-100 / MW-300 (Floors only)
GG-200 or GG-266 / MW-300 (Walls and Floors) |
2 |
6” Steel Duct (28 gauge) |
No |
Concrete Slab / Block Wall |
No |
8 in. diam |
C-AJ-7109 |
SL-100 / MW-300
(Floors
only) GG-200 or GG-266 / MW-300 (Walls and Floors) |
2 |
8” Steel Duct (26 gauge) |
No |
Concrete Slab / Block Wall |
No |
10 in. diam |
C-AJ-7099 |
GG-200 or GG-266 / MW-300
(Walls and Floors) |
2 |
24” by 12” Steel Duct |
No |
Concrete Slab / Block Wall |
No |
325 sq. in. |
C-AJ-7064 |
SL-100 / MW-300 (Floors only)
GG-200 / MW-300 (Walls and Floors) |
2 |
36" Steel |
No |
Concrete Slab /
Block Wall |
No |
24 sq. ft. |
C-AJ-8048 |
SL-100 / MW-300 (
Floors only)
GG-200 / MW-300
(Walls and Floors) |
2 |
6" Copper / 24" Steel |
1” or 1-1/2” Mineral Fiber |
Concrete Slab / Block Wall |
No |
24 sq. ft. |
C-AJ-8048 |
SL-100 / MW-300 / PI-400
(Floors only)
GG-200 / MW-300 / PI-400 (Walls and Floors) |
2 |
FAN COIL UNIT
(2-1/2” Copper) |
1” Glass Fiber |
Concrete Slab / Block Wall |
No |
128 sq. in. |
C-AJ-8090 |
SL-100 / MW-300 (Floors only)
GG-200 / MW-300 (Walls and Floors) |
1 |
LINE SET
(1” Copper) |
3/4” AB / PVC Flexible Foam |
Hollow-Core Floor / Block Wall |
No |
4 in. diam |
C-AJ-8174 |
GG-266 |
2 |
LINE SET
(1” Copper) |
3/4” AB / PVC Flexible Foam |
Hollow-Core Floor / Block Wall |
No |
4 in. diam |
C-AJ-8091 |
GG-266 |
2
(T Rating) |
Vitreous Water Closet with 3” Cast Iron Drain (Compression Coupling) |
No |
Concrete Slab |
No |
4-1/2 in. diam or 4-1/2 by 5-1/2 in. Cone Shape |
F-B-1015 |
GG-200 / MW-300 |
2 |
4” Copper / 8” Steel |
No |
Metal Deck |
Steel |
10-1/2 in. diam |
F-A-1026 |
SL-100, GG-200 or GG-266
/ MW-300 |
1 |
4” Copper / 4” Steel / 1” & 2” Flexible Gas Pipe |
No |
Concrete Slab – Drywall Ceiling |
No |
5-1/2 in. diam |
F-E-1019 |
GG-200 or GG-266 |
- TOP -
CONCRETE – NONMETALLIC PIPE |
1 and 2 |
Multiple 3/4” PE-AL-PE, PEX-AL-PEX Composite Tubing |
No |
Hollow-Core Floor / Block Wall |
No |
3 in. diam |
C-AJ-2365 |
GG-266 |
2 |
Multiple 1” PEX, 3/4” PE- AL-PE, 3/4” PEX-AL-PEX Composite Tubing |
No |
2-1/2” Concrete Slab / Block Wall |
No |
4 in. diam |
C-AJ-2443 |
GG-266 |
2 |
Multiple 1” PEX |
No |
Concrete Slab / Block Wall |
No |
48 sq. in. |
C-AJ-2504 |
GG-266 |
2 |
1-1/2” FRPP |
No |
Concrete Slab / Block Wall |
No |
3-1/8 in. diam |
C-AJ-2440 |
GG-266 |
2 |
2” FRPP |
No |
2-1/2” Concrete Slab / Block Wall |
No |
3-1/2 in. diam |
C-AJ-2546 |
GG-266 |
1 |
2” FRPP |
No |
Hollow-Core Floor / Block Wall |
No |
3 in. diam |
C-AJ-2548 |
GG-266 |
1, 2 and 3 |
2” PVC, CPVC, ABS, PEX |
No |
Hollow-Core Floor / Block Wall |
Steel |
3 in. diam |
C-AJ-2314 and
C-AJ-2587 |
GG-266 |
2 and 3 |
2” PVC, CPVC, ABS, PEX |
No |
Concrete Slab |
Steel |
3 in. diam |
C-AJ-2315 and
C-AJ-2585 |
GG-266 |
2 |
2” PVC, CPVC, ABS, PEX |
No |
2-1/2” Concrete Slab |
No |
3 in. diam |
C-AJ-2406 |
GG-266 |
2 |
2” PVC, CPVC, ABS |
No |
Concrete Slab / Block Wall |
No |
4 in. diam |
C-AJ-2537 |
GG-266 |
2 |
2” PVC, CPVC, ABS, PEX |
No |
2-1/2” Concrete Slab |
No |
3 in. diam |
F-A-2105 |
SL-100, GG-200 or GG-266 / FIREBAND |
2 |
2” PVC, PEX |
No |
Concrete Slab |
No |
2-1/2 to 3-1/4 in. Cone Shape |
F-A-2116 |
GG-266 |
2 |
3” PVC, CPVC, ABS |
No |
Concrete Slab |
No |
5 to 5-1/4 in. Cone Shape |
F-B-2024 |
GG-266 |
2 |
3” XFR |
No |
Concrete Slab / Block Wall |
No |
4-1/2 to 5-1/2 in. Cone Shape |
C-BJ-2030 |
GG-266 / MW-300 / GG-200 |
2 |
4” PVC, CPVC, ABS |
No |
Concrete Slab |
No |
5-1/2 to 6-1/4 in. Cone Shape |
F-B-2028 |
GG-266 |
2 |
4” PVC, CPVC, ABS |
No |
Concrete Slab / Block Wall |
No |
6-1/4 in. diam |
C-BJ-2027 |
GG-266 |
2 |
4” XFR |
No |
Concrete Slab / Block Wall |
No |
5-1/4 to 6-1/2 in. or 6-1/4 to 7-1/2 in. Cone Shape |
C-BJ-2029 |
GG-266 |
2 |
2” PVC, ABS TUB DRAIN |
No |
Concrete Slab |
Steel (Req’d) |
40 sq. in. |
F-A-2132 |
SL-100, GG-200 or GG-266 / FIREBAND / MW-300 |
1 |
2” PVC, ABS |
No |
Concrete Slab |
No |
96 sq. in. |
F-A-2111 |
SL-100, GG-200 or GG-266 / TYPE-SSC / MW-300 |
2 |
2-1/4” Beverage Line (12 x 3/8” FRPE / Metallized Film / Fiberglass Jacket) |
No |
Concrete Slab /
Block Wall |
No |
3-1/8 in. diam |
C-AJ-2441 |
GG-266 / TYPE-SSC |
2 |
3-1/2” Beverage Line (12 x 1/2” PE or PEX, 2 x 3/8” Copper Freon) |
3/4” AB / PVC Flexible Foam |
Concrete Slab / Block Wall |
No |
4-1/2 in. diam |
C-AJ-8136 |
GG-266 / TYPE-SSC |
2 |
3” Glass |
No |
Concrete Slab / Block Wall |
No |
4 in. diam |
C-AJ-2503 |
GG-200 or GG-266 / MW-300 |
2 |
3” PVC, CPVC / 2” PEX |
No |
Concrete Slab / Block Wall |
No |
4-5/8 in diam. |
C-AJ-2439 |
GG-200 or GG-266 / FIREBAND |
2 |
4” PVDF |
No |
Concrete Slab / Block Wall |
No |
5 in. diam |
C-AJ-2405 |
GG-200 or GG-266 / TYPE-SSC / MW-300 |
2 and 3 |
4” PVC, CPVC, ABS, FRPP, XFR |
No |
Concrete Slab / Block Wall |
No |
5 in. diam |
C-AJ-2207 |
GG-200 or GG-266 / TYPE-SSC |
2 |
6” PVC, CPVC |
No |
Concrete Slab / Block Wall |
No |
7 in. diam |
C-AJ-2584 |
GG-200 or GG-266 / TYPE-SSC |
2 |
2 x 1” PEX + 4” Steel |
No |
Concrete Slab / Block Wall |
No |
8 in. diam |
C-BJ-8018 |
GG-266 / MW-300 |
2 |
Multiple 1” PEX, 3/4” PE- AL-PE, 3/4” PEX-AL-PEX Composite Tubing |
No |
Metal Deck |
No |
4 in. diam |
C-AJ-2443 |
GG-266 |
2 |
2” PVC, CPVC, ABS, PEX |
No |
Metal Deck |
No |
3 in. diam |
C-AJ-2406 |
GG-266 |
2 |
2” FRPP |
No |
Metal Deck |
No |
3-1/2 in. diam |
C-AJ-2546 |
GG-266 |
2 |
4” PVC, CPVC, ABS /
2” PEX |
No |
Metal Deck |
No |
5 in. diam |
F-A-2086 |
GG-200 / GG-266 / TYPE-SSC |
2 |
3” and 4” PVC, CPVC |
No |
Metal Deck |
Steel (Req’d) |
6 in. diam |
F-A-2133 |
GG-266 / TYPE-SSR / MW-300 |
1, 1-1/2, and 2 |
2” PEX |
No |
Concrete Slab - Drywall Ceiling |
No |
3 in. diam |
F-E-2006 |
GG-266 |
1 |
4” PVC, CPVC,
ABS, 3” XFR |
No |
Concrete Slab – Drywall Ceiling |
No |
5 in. diam |
F-E-2023 |
GG-266 / TYPE-SSC |
- TOP -
GYPSUM WALLBOARD – METALLIC PIPE and DUCTWORK |
1 |
Blank Opening |
No |
G.W.B. |
No |
15 sq. in. |
W-L-0028 |
GG-200 / Type-X Board |
1 and 2 |
Multiple 1” Gas Tubing |
No |
G.W.B. |
No |
4 in. diam |
W-L-1407 |
GG-266 |
1 and 2 |
3" Copper / 8" Steel |
No |
G.W.B. |
No |
10 in. diam |
W-L-1086 |
GG-200 |
1 |
3” Cast Iron Stack with Membrane Stub-Out to 3” Cast Iron or PVC (Shielded Coupling) |
No |
G.W.B. |
No |
4-1/2 in. diam |
W-L-1315 |
GG-266 |
1 and 2 |
4” Copper, Steel
(45° Angle) |
No |
G.W.B. |
No |
5-1/2 in. diam |
W-L-1316 |
GG-200 or GG-266 |
1 and 2 |
4” Cast Iron (Shielded Coupling) (45° Angle) |
No |
G.W.B. |
No |
5-1/2 in. diam |
W-L-1371 |
GG-200 or GG-266 |
1 and 2 |
4” Copper / 8” Steel |
No |
Shaft Wall |
Steel (Req’d) |
11 in. diam |
W-L-1364 |
GG-200 or GG-266 / MW-300 |
1 and 2 |
4” Copper, Steel |
1” Glass or Mineral Fiber |
Shaft Wall |
Steel (Req’d) |
8-1/2 in. diam |
W-L-5234 |
GG-266 / MW-300 |
1 and 2 |
6" Copper / 16" Steel |
1-1/2” Glass or Mineral Fiber |
G.W.B. |
No / Steel |
21-3/4 in. diam |
W-L-5055 |
GG-266 |
1 |
4” Dryer Vent / 8” Steel Duct (26 gauge) |
No |
G.W.B. |
No |
10 in. diam |
W-L-7115 |
GG-200 or GG-266 |
1 and 2 |
24” by 12” or 12” by 12” Steel Duct |
No |
G.W.B |
No |
325 sq. in. |
W-L-7065 |
GG-200 / MW-300 |
1 and 2 |
3" Copper / 4" Steel |
No |
G.W.B. |
No |
585 sq. in. |
W-L-8012 |
GG-200 / MW-300 |
1 and 2 |
6" Copper / 6" Steel |
1” or 1-1/2” Mineral Fiber |
G.W.B. |
No |
585 sq. in. |
W-L-8012 |
GG-200 / MW-300 / PI-400 |
1 |
LINE SET
(1” Copper) |
3/4” AB / PVC Flexible Foam |
G.W.B. |
No |
4 in. diam |
W-L-8070 |
GG-266 |
- TOP -
GYPSUM WALLBOARD – NONMETALLIC PIPE |
1 and 2 |
3/4” PE-AL-PE,
PEX-AL-PEX
Composite Tubing |
No |
G.W.B. |
No |
3 in. diam |
W-L-2289 |
GG-266 |
1 |
Multiple 1” PEX |
No |
G.W.B. |
No |
16 sq. in. |
W-L-2421 |
GG-266 |
2 |
Multiple 1” PEX |
No |
Shaft Wall |
No |
4-1/2 in. diam |
W-L-2398 |
GG-266 |
1 |
2” FRPP |
No |
G.W.B. |
No |
3 in. diam |
W-L-2451 |
GG-266 |
1 and 2 |
2” PVC, CPVC, ABS, PEX |
No |
G.W.B. |
No |
3 in. diam |
W-L-2145 |
GG-266 |
1 and 2 |
2” PVC, CPVC |
No |
Shaft Wall |
No |
3 in. diam |
W-L-2417 |
GG-266 / FIREBAND |
1 |
2 x 3/4” PEX, PE-AL-PE, PEX-AL-PEX, 1-1/2” ABS or 2” PVC, XFR Membrane Penetrations |
No |
G.W.B. |
No |
3-3/8 in. diam |
W-L-2360 |
GG-266 |
1 and 2 |
4” PVC, CPVC, ABS,
3” XFR |
No |
G.W.B. |
No |
5 in. diam |
W-L-2143 |
GG-200 or GG-266 / TYPE-SSC |
- TOP -
FRAMED FLOOR – METALLIC and NONMETALLIC PIPES |
1 |
4” Copper, Steel (Optional Chase Wall) |
No |
Wood Floor |
No |
5-1/2 in. diam |
F-C-1093 |
GG-200 |
1 |
4” Copper, Steel (Optional Chase Wall) |
No |
ISPAN System |
No |
5-1/2 in. diam |
F-C-1151 |
GG-200 |
1 |
2” Copper, Steel (Optional Chase Wall) |
1/2 to 1” Glass or Mineral Fiber, 1/2 to 3/4” AB / PVC Flexible Foam |
Wood Floor |
No |
4-1/2 in. diam |
F-C-5080 |
GG-266 |
1 |
Multiple 2” PEX, 3/4” PE-AL-PE, 3/4” PEX-AL-PEX Composite Tubing (Optional Chase Wall) |
No |
Wood Floor |
No |
4-1/2 in. diam |
F-C-2228 |
GG-266 |
1 |
2” PVC, CPVC,
ABS, PEX
(Optional Chase Wall) |
No |
Wood Floor |
No |
3 in. diam |
F-C-2200 |
GG-266 |
1 |
3” PVC, CPVC, ABS, XFR with 3” Branch Pipe or 2” P-Trap
(Optional Chase Wall) |
No |
Wood Floor |
No |
4 in. diam |
F-C-2345 |
GG-266 / TYPE-SSC |
1 |
4” PVC, CPVC, ABS (Optional Chase Wall) |
No |
Wood Floor |
No |
5 in. diam |
F-C-2227 |
GG-266 / TYPE-SSC |
- TOP -
ARCHITECTUAL LISTING CHART
ASSEMBLY or INTEGRITY RATING
(Hr) |
JOINT TYPE |
JOINT WIDTH |
UL
SYSTEM Nos. |
SELF SEAL®
PRODUCT CODE |
2 |
Curtain Wall to Concrete Floor |
8 in. max |
CW-D-2034 and
CW-D-2035 |
SL-100 / MW-300 |
1 and 2 |
Head of G.W.B. to Metal Deck
(Optional Structural Steel Support) |
1 in. nominal |
HW-D-0382 |
GG-200 / MW-300 |
2 |
Head of Masonry Wall to Metal Deck
(Optional Structural Steel Support) |
1 in. max |
HW-S-0021 and
HW-D-0459 |
GG-200 / MW-300 |
1 and 2 |
Head of G.W.B. to Concrete Floor |
1 in. max |
HW-S-0060 |
GG-200 |
2 |
Concrete Floor Joint Incorporating Membrane
Air Barrier |
4 in. max |
FF-S-1031 |
SL-100 / MW-300 |
2 |
Concrete Floor to Wall Joint Incorporating
Membrane Air Barrier |
4 in. max |
FW-S-1016 |
SL-100 / MW-300 |
3 |
Horizontal Concrete Expansion Joint |
4 in. nominal |
FF-D-1036 |
SL-100 / MW-300 |
3 |
Vertical Concrete Expansion Joint |
4 in. nominal |
WW-D-1036 |
GG-200 / MW-300 |
3 |
Head of Masonry Wall to Concrete Floor |
4 in. nominal |
HW-D-1032 |
GG-200 / MW-300 |
3 |
Concrete Floor to Masonry Wall |
4 in. nominal |
FW-D-1033 |
SL-100 / MW-300 |
2 |
Stair Assembly |
4 in. nominal |
FW-D-1045 |
GG-200 / MW-300 |
- TOP -